  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Overload release current setting800.0 - 2000A
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive integratedNo
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release1200.0 - 20000A
Adjustment range undelayed short-circuit release3000.0 - 30000A
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Rated permanent current Iu2000A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077847R1 | E2.2S-A 2000 Ekip G Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Overload release current setting

800.0 .. 2000A

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

Motor drive integrated

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

With switched-off indicator

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Motor drive optional

Device construction

Built-in device slide-in technique (withdrawable)

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Rated permanent current Iu

2000A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA