Type of control elementPush button
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitConnection at separate chassis part
Overload release current setting100 - 250A
Integrated earth fault protectionYes
Adjustment range short-term delayed short-circuit release150 - 2500A
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
With switched-off indicatorYes
Adjustment range undelayed short-circuit release375 - 3750A
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA