Rated permanent current Iu400A
Number of auxiliary contacts as normally open contact0
Overload release current setting160.0 - 400A
With switched-off indicatorYes
Number of poles4
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Degree of protection (IP)IP30
Motor drive integratedNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Type of control elementPush button
Adjustment range undelayed short-circuit release600.0 - 6000A
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release240.0 - 4000A
Integrated earth fault protectionYes
Motor drive optionalYes
Rated voltage600 - 600V
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally closed contact0
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077864R1 | E2.2V-A 400 Ekip G Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

400A

Number of auxiliary contacts as normally open contact

0

Overload release current setting

160.0 .. 400A

With switched-off indicator

Number of poles

4

Position of connection for main current circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

Degree of protection (IP)

IP30

Motor drive integrated

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Type of control element

Push button

Adjustment range undelayed short-circuit release

600.0 .. 6000A

With under voltage release

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

240.0 .. 4000A

Integrated earth fault protection

Motor drive optional

Rated voltage

600 .. 600V

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit