  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu800 A
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Adjustment range undelayed short-circuit release1200.0 - 12000A
Motor drive optionalYes
Type of electrical connection of main circuitConnection at separate chassis part
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Integrated earth fault protectionNo
Type of control elementPush button
Number of auxiliary contacts as change-over contact4
Rated voltage600 - 600V
Motor drive integratedNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Adjustment range short-term delayed short-circuit release- - -A
Suitable for DIN rail (top hat rail) mountingNo
Number of poles4
With integrated under voltage releaseNo
Overload release current setting320.0 - 800A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077868R1 | E2.2V-A 800 Ekip Dip LI 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

800 A

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Motor drive optional

Type of electrical connection of main circuit

Connection at separate chassis part

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

With switched-off indicator

Integrated earth fault protection

Type of control element

Push button

Number of auxiliary contacts as change-over contact

4

Rated voltage

600 .. 600V

Motor drive integrated

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Adjustment range short-term delayed short-circuit release

- .. -A

Suitable for DIN rail (top hat rail) mounting

Number of poles

4

With integrated under voltage release

Overload release current setting

320.0 .. 800A