Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu800A
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting320.0 - 800A
Number of poles4
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated voltage600 - 600V
Motor drive integratedNo
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Device constructionBuilt-in device slide-in technique (withdrawable)
With under voltage releaseNo
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Complete device with protection unitYes
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release1200.0 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077874R1 | E2.2V-A 800 Ekip G Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

320.0 .. 800A

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated voltage

600 .. 600V

Motor drive integrated

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

Device construction

Built-in device slide-in technique (withdrawable)

With under voltage release

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

With switched-off indicator

DIN rail (top hat rail) mounting optional

Motor drive optional

Complete device with protection unit

Integrated earth fault protection

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Suitable for DIN rail (top hat rail) mounting

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.