Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Rated permanent current Iu1200A
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Number of poles4
Overload release current setting480.0 - 1200A
Motor drive integratedNo
Integrated earth fault protectionNo
Degree of protection (IP)IP30
Rated voltage600 - 600V
Adjustment range undelayed short-circuit release1800.0 - 18000A
Complete device with protection unitYes
Type of control elementPush button
Motor drive optionalYes
Position of connection for main current circuitConnection at separate chassis part
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
With switched-off indicatorYes
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range short-term delayed short-circuit release- - -A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077881R1 | E2.2V-A 1200 Ekip Touch LI 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

1200A

With integrated under voltage release

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Number of poles

4

Overload release current setting

480.0 .. 1200A

Motor drive integrated

Integrated earth fault protection

Degree of protection (IP)

IP30

Rated voltage

600 .. 600V

Adjustment range undelayed short-circuit release

1800.0 .. 18000A

Complete device with protection unit

Type of control element

Push button

Motor drive optional

Position of connection for main current circuit

Connection at separate chassis part

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

With switched-off indicator

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range short-term delayed short-circuit release

- .. -A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.