Technical specifications

Number of poles3
Motor drive integratedNo
Overload release current setting1280.0 - 3200A
Rated permanent current Iu3200A
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release4800.0 - 48000A
Number of auxiliary contacts as change-over contact4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Suitable for DIN rail (top hat rail) mountingNo
With integrated under voltage releaseNo
Motor drive optionalYes
Type of electrical connection of main circuitBolt connection
With switched-off indicatorYes
Device constructionBuilt-in device fixed built-in technique
Type of control elementPush button
Complete device with protection unitYes
Position of connection for main current circuitBack side
Degree of protection (IP)IP30
Integrated earth fault protectionNo
Rated voltage600 - 600V
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA077922R1 | E4.2H-A 3200 Ekip Touch LSI 3p FVR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

3

Motor drive integrated

Overload release current setting

1280.0 .. 3200A

Rated permanent current Iu

3200A

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Number of auxiliary contacts as change-over contact

4

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Suitable for DIN rail (top hat rail) mounting

With integrated under voltage release

Motor drive optional

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

Complete device with protection unit

Position of connection for main current circuit

Back side

Degree of protection (IP)

IP30

Integrated earth fault protection

Rated voltage

600 .. 600V