Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu2500A
Number of poles3
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
With switched-off indicatorYes
Degree of protection (IP)IP30
Overload release current setting1000.0 - 2500A
Rated voltage600 - 600V
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
Adjustment range undelayed short-circuit release3750.0 - 37500A
DIN rail (top hat rail) mounting optionalNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Adjustment range short-term delayed short-circuit release1500.0 - 25000A
Complete device with protection unitYes
Integrated earth fault protectionYes
With under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA078067R1 | E4.2V-A 2500 Ekip G Hi-Touch LSIG 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2500A

Number of poles

3

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Back side

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Degree of protection (IP)

IP30

Overload release current setting

1000.0 .. 2500A

Rated voltage

600 .. 600V

Number of auxiliary contacts as change-over contact

4

Type of control element

Push button

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Complete device with protection unit

Integrated earth fault protection

With under voltage release

Device construction

Built-in device fixed built-in technique

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.