Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Overload release current setting1280 - 3200A
Position of connection for main current circuitBack side
Complete device with protection unitYes
Type of control elementPush button
Motor drive optionalYes
Integrated earth fault protectionNo
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Adjustment range short-term delayed short-circuit release- - -A
With switched-off indicatorYes
Adjustment range undelayed short-circuit release4800 - 48000A
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu3200A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user