Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Overload release current setting1280 - 3200A
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionYes
Type of electrical connection of main circuitBolt connection
Adjustment range undelayed short-circuit release4800 - 48000A
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Complete device with protection unitYes
Adjustment range short-term delayed short-circuit release1920 - 32000A
With switched-off indicatorYes
Device constructionBuilt-in device fixed built-in technique
Type of control elementPush button
Rated permanent current Iu3200A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA