Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA078304R1 | E4.2V-A 3200 Ekip G Touch LSIG 4p FVR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
3200A
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Rated voltage
600 .. 600V
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Motor drive integrated
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
1280.0 .. 3200A
Complete device with protection unit
Degree of protection (IP)
IP30
Integrated earth fault protection
Motor drive optional
Device construction
Built-in device fixed built-in technique
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of control element
Push button
With switched-off indicator