Technical specifications

Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Overload release current setting1000.0 - 2500A
With integrated under voltage releaseNo
Number of poles3
Rated voltage600 - 600V
Degree of protection (IP)IP30
Number of auxiliary contacts as normally open contact0
Type of control elementPush button
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitConnection at separate chassis part
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Adjustment range short-term delayed short-circuit release1500.0 - 25000A
Adjustment range undelayed short-circuit release3750.0 - 37500A
With switched-off indicatorYes
Motor drive optionalYes
Rated permanent current Iu2500A
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA078376R1 | E4.2H-A 2500 Ekip Hi-Touch LSIG 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Position of connection for main current circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

1000.0 .. 2500A

With integrated under voltage release

Number of poles

3

Rated voltage

600 .. 600V

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally open contact

0

Type of control element

Push button

DIN rail (top hat rail) mounting optional

Type of electrical connection of main circuit

Connection at separate chassis part

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

With switched-off indicator

Motor drive optional

Rated permanent current Iu

2500A

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.