Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Motor drive integratedNo
With switched-off indicatorYes
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Degree of protection (IP)IP30
With integrated under voltage releaseNo
Overload release current setting1000 - 2500A
Complete device with protection unitYes
Adjustment range short-term delayed short-circuit release1500 - 25000A
Integrated earth fault protectionYes
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release3750 - 37500A
Rated permanent current Iu2500A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA