Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of poles3
Motor drive integratedNo
With integrated under voltage releaseNo
Rated permanent current Iu3200A
Overload release current setting1280.0 - 3200A
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Rated voltage600 - 600V
Adjustment range undelayed short-circuit release4800.0 - 48000A
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
With switched-off indicatorYes
Type of control elementPush button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Number of auxiliary contacts as change-over contact4
Integrated earth fault protectionNo
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA078532R1 | E4.2V-A 3200 Ekip Touch LSI 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of poles

3

Motor drive integrated

With integrated under voltage release

Rated permanent current Iu

3200A

Overload release current setting

1280.0 .. 3200A

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Rated voltage

600 .. 600V

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

With switched-off indicator

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Number of auxiliary contacts as change-over contact

4

Integrated earth fault protection

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.