Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA078532R1 | E4.2V-A 3200 Ekip Touch LSI 3p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Motor drive integrated
With integrated under voltage release
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Rated voltage
600 .. 600V
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
With switched-off indicator
Type of control element
Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Complete device with protection unit