Technical specifications

Rated permanent current Iu3200A
Number of auxiliary contacts as normally closed contact0
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
Adjustment range undelayed short-circuit release4800.0 - 48000A
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitConnection at separate chassis part
Overload release current setting1280.0 - 3200A
Degree of protection (IP)IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Type of electrical connection of main circuitConnection at separate chassis part
Number of poles3
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
Type of control elementPush button
With switched-off indicatorYes
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionYes
Motor drive optionalYes
Rated voltage600 - 600V
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA078537R1 | E4.2V-A 3200 Ekip G Hi-Touch LSIG 3p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

3200A

Number of auxiliary contacts as normally closed contact

0

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Number of auxiliary contacts as normally open contact

0

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

1280.0 .. 3200A

Degree of protection (IP)

IP30

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Type of electrical connection of main circuit

Connection at separate chassis part

Number of poles

3

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

Type of control element

Push button

With switched-off indicator

Motor drive integrated

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Motor drive optional

Rated voltage

600 .. 600V

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.