Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive integratedNo
Degree of protection (IP)IP30
Type of control elementPush button
Overload release current setting1000 - 2500A
Adjustment range undelayed short-circuit release3750 - 37500A
Adjustment range short-term delayed short-circuit release1500 - 25000A
Position of connection for main current circuitConnection at separate chassis part
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact4
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Motor drive optionalYes
Rated permanent current Iu2500A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA