Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles4
Rated permanent current Iu3200A
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Overload release current setting1280.0 - 3200A
With switched-off indicatorYes
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Rated voltage600 - 600V
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
Integrated earth fault protectionYes
DIN rail (top hat rail) mounting optionalNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Adjustment range undelayed short-circuit release4800.0 - 48000A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA078616R1 | E4.2H-A 3200 Ekip Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Rated permanent current Iu

3200A

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

Overload release current setting

1280.0 .. 3200A

With switched-off indicator

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

Motor drive integrated

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Rated voltage

600 .. 600V

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.