Technical specifications

Overload release current setting1000.0 - 2500A
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Motor drive integratedNo
Adjustment range undelayed short-circuit release3750.0 - 37500A
Adjustment range short-term delayed short-circuit release1500.0 - 25000A
Integrated earth fault protectionYes
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu2500A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA078696R1 | E4.2S-A 2500 Ekip Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

1000.0 .. 2500A

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Motor drive integrated

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Integrated earth fault protection

Motor drive optional

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

Rated permanent current Iu

2500A

Number of poles

4

Rated voltage

600 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA