Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA079009R1 | E6.2V-A 4000 Ekip Dip LSI 4p F HR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
1600.0 .. 4000A
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
With integrated under voltage release
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
With switched-off indicator
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Motor drive optional
Rated permanent current Iu
4000A
Number of poles
4
Rated voltage
600 .. 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA