Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Motor drive integratedNo
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release2400 - 40000A
With integrated under voltage releaseNo
Adjustment range undelayed short-circuit release6000 - 60000A
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
With switched-off indicatorYes
Overload release current setting1600 - 4000A
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Integrated earth fault protectionYes
Complete device with protection unitYes
Rated permanent current Iu4000A
Number of poles4
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user