Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu5000A
Number of auxiliary contacts as normally open contact0
Number of poles4
Overload release current setting2000.0 - 5000A
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Device constructionBuilt-in device slide-in technique (withdrawable)
Position of connection for main current circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release7500.0 - 75000A
Rated voltage600 - 600V
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
With under voltage releaseNo
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Type of control elementPush button
Motor drive optionalYes
Adjustment range short-term delayed short-circuit release3000.0 - 50000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Integrated earth fault protectionYes
Type of electrical connection of main circuitConnection at separate chassis part
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA079443R1 | E6.2H-A/f 5000 Ekip Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

5000A

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Overload release current setting

2000.0 .. 5000A

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Device construction

Built-in device slide-in technique (withdrawable)

Position of connection for main current circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

7500.0 .. 75000A

Rated voltage

600 .. 600V

Suitable for DIN rail (top hat rail) mounting

Complete device with protection unit

With under voltage release

Motor drive integrated

DIN rail (top hat rail) mounting optional

With switched-off indicator

Type of control element

Push button

Motor drive optional

Adjustment range short-term delayed short-circuit release

3000.0 .. 50000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.