Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA079503R1 | E6.2V-A/f 5000 Ekip Touch LSIG 4p WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of poles
4
Rated permanent current Iu
5000A
Degree of protection (IP)
IP30
Rated voltage
600 .. 600V
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Overload release current setting
2000.0 .. 5000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
With under voltage release
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button