Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting1000.0 - 2500A
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
Rated permanent current Iu2500A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of poles4
Position of connection for main current circuitBack side
Rated voltage900 - 900V
Degree of protection (IP)IP30
Motor drive integratedNo
Device constructionBuilt-in device fixed built-in technique
Type of control elementPush button
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release1500.0 - 25000A
Adjustment range undelayed short-circuit release3750.0 - 37500A
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA104372R1 | E2.2H/E9 2500 Ekip Dip LSI 4p FHR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

1000.0 .. 2500A

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

Rated permanent current Iu

2500A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Position of connection for main current circuit

Back side

Rated voltage

900 .. 900V

Degree of protection (IP)

IP30

Motor drive integrated

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.