Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as change-over contact4
Overload release current setting1000 - 2500A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Position of connection for main current circuitBack side
Motor drive integratedNo
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release1500 - 25000A
Degree of protection (IP)IP30
Type of control elementPush button
Type of electrical connection of main circuitBolt connection
Motor drive optionalYes
Adjustment range undelayed short-circuit release3750 - 37500A
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Rated permanent current Iu2500A
Number of poles4
Rated voltage900 - 900V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user