Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Overload release current setting2520 - 6300A
Number of auxiliary contacts as change-over contact4
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release9450 - 94500A
Type of control elementPush button
Adjustment range short-term delayed short-circuit release3780 - 63000A
With switched-off indicatorYes
Device constructionBuilt-in device slide-in technique (withdrawable)
With under voltage releaseNo
Integrated earth fault protectionYes
Motor drive optionalYes
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu6300A
Number of poles4
Rated voltage900 - 900V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA