Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Degree of protection (IP)IP30
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Overload release current setting2520 - 6300A
With switched-off indicatorYes
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Adjustment range short-term delayed short-circuit release3780 - 63000A
Adjustment range undelayed short-circuit release9450 - 94500A
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
Rated permanent current Iu6300A
Number of poles3
Rated voltage900 - 900V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA