Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Built-in depth
82.5mm
Rated voltage
400V
Rated insulation voltage Ui
690V
Release characteristic
D
Number of protected poles
2
Rated impulse withstand voltage Uimp
6kV
Voltage type
Other
Power loss
16W
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Frequency
50 - 60Hz
Number of poles (total)
2
Current limiting class
3
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
15kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
50kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
30kA
Rated current
100A
Width in number of modular spacings
3
Ambient temperature during operating
-25 - 60°C
Connectable conductor cross section solid-core
1 - 70mm²
Connectable conductor cross section multi-wired
1 - 50mm²
Over voltage category
3
Flush-mounted installation
No
Explosion-proof
No
Concurrently switching neutral conductor
No
Degree of protection (IP)
IP20
Pollution degree
3
Additional equipment possible
Yes
From same serie
2CCG001242R0001 | S802P-D100

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Built-in depth
82.5mm
Rated voltage
400V
Rated insulation voltage Ui
690V
Release characteristic
D
Number of protected poles
2
Rated impulse withstand voltage Uimp
6kV
Voltage type
Other
Power loss
16W
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Frequency
50 .. 60Hz
Number of poles (total)
2
Current limiting class
3
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
15kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
50kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
30kA
Rated current
100A
Width in number of modular spacings
3
Ambient temperature during operating
-25 .. 60°C
Connectable conductor cross section solid-core
1 .. 70mm²
Connectable conductor cross section multi-wired
1 .. 50mm²
Over voltage category
3
Flush-mounted installation
Explosion-proof
Concurrently switching neutral conductor
Degree of protection (IP)
IP20
Pollution degree
3
Additional equipment possible