Rated insulation voltage Ui690V
Number of poles (total)3
Built-in depth82.5mm
Release characteristicK
Rated impulse withstand voltage Uimp6kV
Rated current125A
Number of protected poles3
Rated voltage400V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V-kA
Frequency50 - 60Hz
Power loss28.2W
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V15kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V50kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V-kA
Current limiting class3
Voltage typeOther
Degree of protection (IP)IP20
Concurrently switching neutral conductorNo
Ambient temperature during operating-25 - 60°C
Width in number of modular spacings5
Flush-mounted installationNo
Additional equipment possibleYes
Pollution degree3
Connectable conductor cross section multi-wired1 - 50mm²
Explosion-proofNo
Connectable conductor cross section solid-core1 - 70mm²
Over voltage category3
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CCG001258R0001 | S803P-K125

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Rated insulation voltage Ui

690V

Number of poles (total)

3

Built-in depth

82.5mm

Release characteristic

K

Rated impulse withstand voltage Uimp

6kV

Rated current

125A

Number of protected poles

3

Rated voltage

400V

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

-kA

Frequency

50 .. 60Hz

Power loss

28.2W

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

15kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

50kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

-kA

Current limiting class

3

Voltage type

Other

Degree of protection (IP)

IP20

Concurrently switching neutral conductor

Ambient temperature during operating

-25 .. 60°C

Width in number of modular spacings

5

Flush-mounted installation

Additional equipment possible

Pollution degree

3

Connectable conductor cross section multi-wired

1 .. 50mm²

Explosion-proof

Connectable conductor cross section solid-core

1 .. 70mm²

Over voltage category

3