Technical specifications

Built-in depth69mm
Rated current16A
Rated insulation voltage Ui500V
Number of poles (total)1
Number of protected poles1
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V-kA
Rated voltage240V
Rated impulse withstand voltage Uimp6kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V25kA
Power loss1.6W
Release characteristicD
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V-kA
Voltage typeOther
Current limiting class-
Frequency50 - 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V-kA
Additional equipment possibleYes
Pollution degree3
Over voltage category4
Ambient temperature during operating-40 - 70°C
Flush-mounted installationNo
Explosion-proofNo
Connectable conductor cross section solid-core0.75 - 35mm²
Degree of protection (IP)IP20
Width in number of modular spacings1.0
Connectable conductor cross section multi-wired0.75 - 25mm²
Concurrently switching neutral conductorNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS381001R0161 | S301P-D16

Main Product Image

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Built-in depth

69mm

Rated current

16A

Rated insulation voltage Ui

500V

Number of poles (total)

1

Number of protected poles

1

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

-kA

Rated voltage

240V

Rated impulse withstand voltage Uimp

6kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

25kA

Power loss

1.6W

Release characteristic

D

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

-kA

Voltage type

Other

Current limiting class

-

Frequency

50 .. 60Hz

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

-kA

Additional equipment possible

Pollution degree

3

Over voltage category

4

Ambient temperature during operating

-40 .. 70°C

Flush-mounted installation

Explosion-proof

Connectable conductor cross section solid-core

0.75 .. 35mm²

Degree of protection (IP)

IP20

Width in number of modular spacings

1.0

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Concurrently switching neutral conductor