2CDS382001R0101 | S302P-D10
Code: 1997211

2CDS382001R0101 | S302P-D10

Number of protected poles
2
Rated current
10A
Number of poles (total)
2
Rated insulation voltage Ui
500V
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
-kA
Rated voltage
415V
Rated impulse withstand voltage Uimp
6kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
25kA
Frequency
50 .. 60Hz
Voltage type
Other
Built-in depth
69mm
Power loss
2.4W
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Release characteristic
D
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Current limiting class
-
Concurrently switching neutral conductor
Degree of protection (IP)
IP20
Width in number of modular spacings
2.0
Explosion-proof
Additional equipment possible
Pollution degree
3
Flush-mounted installation
Ambient temperature during operating
-40 .. 70°C
Connectable conductor cross section multi-wired
0.75 .. 25mm²
Connectable conductor cross section solid-core
0.75 .. 35mm²
Over voltage category