2CDS382001R0401 | S302P-D40
Code: 1997245

2CDS382001R0401 | S302P-D40

Rated current
40A
Power loss
5.8W
Release characteristic
D
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
20kA
Rated insulation voltage Ui
500V
Rated voltage
415V
Number of protected poles
2
Current limiting class
-
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Number of poles (total)
2
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
-kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Built-in depth
69mm
Frequency
50 .. 60Hz
Voltage type
Other
Rated impulse withstand voltage Uimp
6kV
Pollution degree
3
Width in number of modular spacings
2.0
Concurrently switching neutral conductor
Connectable conductor cross section solid-core
0.75 .. 35mm²
Over voltage category
4
Flush-mounted installation
Degree of protection (IP)
IP20
Ambient temperature during operating
-40 .. 70°C
Additional equipment possible
Explosion-proof
Connectable conductor cross section multi-wired