Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Built-in depth
82.5mm
Rated insulation voltage Ui
690V
Rated voltage
230V
Rated current
2.5A
Release characteristic
D
Number of poles (total)
1
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
25kA
Number of protected poles
1
Voltage type
Other
Rated impulse withstand voltage Uimp
8kV
Frequency
50 - 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
50kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
25kA
Power loss
2.5W
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
6kA
Current limiting class
3
Flush-mounted installation
Yes
Concurrently switching neutral conductor
Yes
Over voltage category
4
Pollution degree
3
Width in number of modular spacings
1.5
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
0 - 50mm²
Additional equipment possible
Yes
Explosion-proof
No
Ambient temperature during operating
-25 - 60°C
Connectable conductor cross section solid-core
0 - 70mm²
2CCF019861R0001 | S801S-D2.5

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Built-in depth
82.5mm
Rated insulation voltage Ui
690V
Rated voltage
230V
Rated current
2.5A
Release characteristic
D
Number of poles (total)
1
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
25kA
Number of protected poles
1
Voltage type
Other
Rated impulse withstand voltage Uimp
8kV
Frequency
50 .. 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
50kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
25kA
Power loss
2.5W
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
6kA
Current limiting class
3
Flush-mounted installation
Concurrently switching neutral conductor
Over voltage category
4
Pollution degree
3
Width in number of modular spacings
1.5
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
0 .. 50mm²
Additional equipment possible
Explosion-proof
Ambient temperature during operating
-25 .. 60°C
Connectable conductor cross section solid-core
0 .. 70mm²
We use cookies to enhance your experience.