Technical specifications
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
30kA
Frequency
50 .. 60Hz
Rated current
0.5A
Power loss
4W
Current limiting class
3
Built-in depth
82.5mm
Rated impulse withstand voltage Uimp
8kV
Number of protected poles
2
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
50kA
Rated insulation voltage Ui
690V
Voltage type
Other
Number of poles (total)
2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Rated voltage
400V
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
25kA
Release characteristic
K
Connectable conductor cross section solid-core
0 .. 70mm²
Degree of protection (IP)
IP20
Additional equipment possible
Explosion-proof
Over voltage category
4
Width in number of modular spacings
3
Flush-mounted installation
Concurrently switching neutral conductor
Ambient temperature during operating
-25 .. 60°C
Connectable conductor cross section multi-wired
0 .. 50mm²
Pollution degree
3