Technical specifications

Voltage typeAC
Built-in depth91mm
Pollution degree2
Rated current20A
Width in number of modular spacings4
Release characteristicB
Rated insulation voltage Ui500V
Leakage current typeF
Power loss7.5W
Surge current capacity3kA
Degree of protection (IP)IP20
Over voltage category3
Current limiting class3
Frequency50/60 Hz
Rated voltage415V
Rated fault current0.03A
Concurrently switching neutral conductorYes
Connectable conductor cross section solid-core- - -mm²
Number of protected poles3
Number of poles (total)4
With interlocking deviceYes
Flush-mounted installationNo
Suitable for flush-mounted installationNo
Ambient temperature during operating-25 - 60°C
Rated short-circuit breaking capacity according to IEC 60947-215kA
Connectable conductor cross section multi-wired0.75 - 25mm²
Disconnection characteristicUndelayed
Rated short-circuit breaking capacity Icn according to EN 61009-110kA
Anti-nuisance tripping versionNo
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity according to EN 6100910kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CCL563310E0205 | FS403MK-B20/0.03

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Voltage type

AC

Built-in depth

91mm

Pollution degree

2

Rated current

20A

Width in number of modular spacings

4

Release characteristic

B

Rated insulation voltage Ui

500V

Leakage current type

F

Power loss

7.5W

Surge current capacity

3kA

Degree of protection (IP)

IP20

Over voltage category

3

Current limiting class

3

Frequency

50/60 Hz

Rated voltage

415V

Rated fault current

0.03A

Concurrently switching neutral conductor

Connectable conductor cross section solid-core

- .. -mm²

Number of protected poles

3

Number of poles (total)

4

With interlocking device

Flush-mounted installation

Suitable for flush-mounted installation

Ambient temperature during operating

-25 .. 60°C

Rated short-circuit breaking capacity according to IEC 60947-2

15kA

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Disconnection characteristic

Undelayed

Rated short-circuit breaking capacity Icn according to EN 61009-1

10kA

Anti-nuisance tripping version

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity according to EN 61009

10kA