Details

  • Circuit breakers and fuses
  • Residual current circuit breaker (RCCB)
  • 1 KOM
  • ABB

Technical specifications

Built-in depth69mm
Mounting methodOther
Short-circuit breaking capacity (Icw)1kA
FrequencyOther
Selective protectionYes
Pollution degree2
Explosion-proofNo
Short-time delayed trippingYes
Power loss9.6W
Degree of protection (IP)IP20
RAL-number (similar)-
Surge current capacity0.25kA
Width in number of modular spacings4
Rated insulation voltage Ui500V
Connectable conductor cross section solid-core- - -mm²
Connectable conductor cross section multi-wired- - -mm²
Rated impulse withstand voltage Uimp4kV
Additional equipment possibleYes
With interlocking deviceYes
Ambient temperature during operating-25 - 40°C
Rated current40A
Rated voltage400V
Number of poles4
Rated fault current0.1A
Leakage current typeA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user