2CCS572001R1168 | S402M-UCZ16
Code: 2002127

2CCS572001R1168 | S402M-UCZ16

Built-in depth
75mm
Release characteristic
Other
Number of poles (total)
2
Number of protected poles
2
Rated current
16A
Rated voltage
400V
Rated insulation voltage Ui
440V
Rated impulse withstand voltage Uimp
4kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
10kA
Voltage type
Other
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
25kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Power loss
5.2W
Frequency
50 .. 60Hz
Current limiting class
3
Flush-mounted installation
Concurrently switching neutral conductor
Over voltage category
3
Pollution degree
2
Additional equipment possible
Width in number of modular spacings
2
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 .. 60°C
Connectable conductor cross section multi-wired
0.75 .. 25mm²
Connectable conductor cross section solid-core
0.75 .. 35mm²
Explosion-proof