Details
- •Circuit breakers and fuses
- •Miniature circuit breaker (MCB)
- •1 KOM
- •ABB
Technical specifications
2CDS273347R0087 | SU203MR-K0.2

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Number of poles (total)
3
Release characteristic
K
Built-in depth
69mm
Rated voltage
400V
Rated impulse withstand voltage Uimp
4kV
Number of protected poles
3
Rated insulation voltage Ui
440V
Rated current
0.2A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
15kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
10kA
Voltage type
Other
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
10kA
Frequency
50 .. 60Hz
Power loss
5.1W
Current limiting class
3
Concurrently switching neutral conductor
Connectable conductor cross section solid-core
0.75 .. 35mm²
Pollution degree
3
Width in number of modular spacings
3.0
Ambient temperature during operating
-25 .. 55°C
Degree of protection (IP)
IP20
Over voltage category
3
Flush-mounted installation
Additional equipment possible
Connectable conductor cross section multi-wired
0.75 .. 25mm²
Explosion-proof