Aleta.hr
Main Product Image

2CDS273347R0467 | SU203MR-K16

Code: 2003263

ManufacturerABB
Catalog number2CDS273347R0467
EAN code4016779958479

















Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Number of protected poles3
Rated current16A
Release characteristicK
Built-in depth69mm
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Rated voltage400V
Number of poles (total)3
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Rated insulation voltage Ui440V
Rated impulse withstand voltage Uimp4kV
Frequency50 - 60Hz
Current limiting class3
Voltage typeOther
Power loss7.5W
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V15kA
Additional equipment possibleYes
Degree of protection (IP)IP20
Flush-mounted installationNo
Over voltage category3
Concurrently switching neutral conductorNo
Connectable conductor cross section solid-core0.75 - 35mm²
Connectable conductor cross section multi-wired0.75 - 25mm²
Pollution degree3
Width in number of modular spacings3.0
Explosion-proofNo
Ambient temperature during operating-25 - 55°C
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS273347R0467 | SU203MR-K16

Main Product Image

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Number of protected poles

3

Rated current

16A

Release characteristic

K

Built-in depth

69mm

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Rated voltage

400V

Number of poles (total)

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Rated insulation voltage Ui

440V

Rated impulse withstand voltage Uimp

4kV

Frequency

50 .. 60Hz

Current limiting class

3

Voltage type

Other

Power loss

7.5W

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

15kA

Additional equipment possible

Degree of protection (IP)

IP20

Flush-mounted installation

Over voltage category

3

Concurrently switching neutral conductor

Connectable conductor cross section solid-core

0.75 .. 35mm²

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Pollution degree

3

Width in number of modular spacings

3.0

Explosion-proof

Ambient temperature during operating

-25 .. 55°C

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.