Rated voltage230V
Release characteristicB
Built-in depth72mm
Rated fault current0.03A
Pollution degree3
Leakage current typeA
Rated insulation voltage Ui440V
Rated current32A
Current limiting class3
Over voltage category3
Voltage typeAC
Width in number of modular spacings2
Surge current capacity0.25kA
Degree of protection (IP)IP20
Number of protected poles2
Frequency50 Hz
Power loss7.60W
Ambient temperature during operating-25 - 55°C
With interlocking deviceNo
Connectable conductor cross section multi-wired1 - 25mm²
Flush-mounted installationNo
Number of poles (total)2
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity according to IEC 60947-210kA
Connectable conductor cross section solid-core- - -mm²
Concurrently switching neutral conductorYes
Rated short-circuit breaking capacity according to EN 610096kA
Disconnection characteristicUndelayed
Anti-nuisance tripping versionNo
Rated short-circuit breaking capacity Icn according to EN 61009-16kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CSR752140R1325 | DS202CR B32 A30

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

230V

Release characteristic

B

Built-in depth

72mm

Rated fault current

0.03A

Pollution degree

3

Leakage current type

A

Rated insulation voltage Ui

440V

Rated current

32A

Current limiting class

3

Over voltage category

3

Voltage type

AC

Width in number of modular spacings

2

Surge current capacity

0.25kA

Degree of protection (IP)

IP20

Number of protected poles

2

Frequency

50 Hz

Power loss

7.60W

Ambient temperature during operating

-25 .. 55°C

With interlocking device

Connectable conductor cross section multi-wired

1 .. 25mm²

Flush-mounted installation

Number of poles (total)

2

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity according to IEC 60947-2

10kA

Connectable conductor cross section solid-core

- .. -mm²

Concurrently switching neutral conductor

Rated short-circuit breaking capacity according to EN 61009

6kA

Disconnection characteristic

Undelayed

Anti-nuisance tripping version

Rated short-circuit breaking capacity Icn according to EN 61009-1

6kA