Technical specifications

Number of poles (total)2
Rated impulse withstand voltage Uimp4kV
Rated voltage110V
Number of protected poles2
Rated current16A
Rated fault current0.03A
Rated insulation voltage Ui440V
Current limiting class3
Power loss4.20W
Disconnection characteristicUndelayed
Rated short-circuit breaking capacity according to EN 6100910kA
Surge current capacity0.25kA
Rated short-circuit breaking capacity Icn according to EN 61009-110kA
Rated short-circuit breaking capacity according to IEC 60947-210kA
Voltage typeAC
Leakage current typeA
Width in number of modular spacings2
Built-in depth72mm
Frequency50/60 Hz
Release characteristicC
Pollution degree3
Degree of protection (IP)IP20
Concurrently switching neutral conductorYes
With interlocking deviceNo
Flush-mounted installationNo
Connectable conductor cross section solid-core- - -mm²
Ambient temperature during operating-25 - 55°C
Over voltage category3
Anti-nuisance tripping versionNo
Connectable conductor cross section multi-wired1 - 25mm²
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CSR772199R1164 | DS202CR M C16 A30 110V

Main Product Image

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Number of poles (total)

2

Rated impulse withstand voltage Uimp

4kV

Rated voltage

110V

Number of protected poles

2

Rated current

16A

Rated fault current

0.03A

Rated insulation voltage Ui

440V

Current limiting class

3

Power loss

4.20W

Disconnection characteristic

Undelayed

Rated short-circuit breaking capacity according to EN 61009

10kA

Surge current capacity

0.25kA

Rated short-circuit breaking capacity Icn according to EN 61009-1

10kA

Rated short-circuit breaking capacity according to IEC 60947-2

10kA

Voltage type

AC

Leakage current type

A

Width in number of modular spacings

2

Built-in depth

72mm

Frequency

50/60 Hz

Release characteristic

C

Pollution degree

3

Degree of protection (IP)

IP20

Concurrently switching neutral conductor

With interlocking device

Flush-mounted installation

Connectable conductor cross section solid-core

- .. -mm²

Ambient temperature during operating

-25 .. 55°C

Over voltage category

3

Anti-nuisance tripping version

Connectable conductor cross section multi-wired

1 .. 25mm²