Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Motor drive integratedNo
Degree of protection (IP)IP20
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Overload release current setting480 - 1200A
Adjustment range undelayed short-circuit release1200 - 12000A
Adjustment range short-term delayed short-circuit release1200 - 12000A
With switched-off indicatorNo
DIN rail (top hat rail) mounting optionalYes
Type of control elementToggle
Type of electrical connection of main circuitBolt connection
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Integrated earth fault protectionNo
Rated permanent current Iu1200A
Number of poles3
Rated voltage240 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA

From same serie