Technical specifications
SPA412

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Earthing, lightning and surge protection
- Combined arrester for power supply systems
- 1 KOM
- HAGER
Technical specifications
Remote signalling
Max. continuous voltage AC
264V
Mounting method
DIN rail (top hat rail) 35 mm
Follow current extinguishing capability
25kA
Construction size
4 modular spacing
Max. conductor cross section flexible (fine-strand)
25mm²
Voltage protection level N-PE
1.5kV
Max. conductor cross section solid (solid, stranded)
35mm²
Signalling at the device
Optic
System configuration TN-C-S
System configuration DC
Specific energy (W/R)
39kJ/Ohm
Voltage switching spark gap technology
Integrated backup fuse
Overcurrent protected voltage tapping
System configuration TN
System configuration other
System configuration TT
System configuration IT
Voltage protection level L-PE
2.5kV
Max. overcurrent protection device, parallel connection (fuse)
160A
Test class
Type 1 and 2 and 3
System configuration TN-C
System configuration TN-S
Max. overcurrent protection device, series connection (fuse)
80A
Voltage protection level L-N
1.5kV
Lightning impulse current (10/350 µs)
12.5kA
Number of poles
4
Voltage protection level
1.5kV
Nominal voltage AC
415V
Degree of protection (IP)
IP20