Details
- •Earthing, lightning and surge protection
- •Combined arrester for power supply systems
- •1 KOM
- •HAGER
Technical specifications
SPA931

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Earthing, lightning and surge protection
- Combined arrester for power supply systems
- 1 KOM
- HAGER
Technical specifications
Number of poles
4
Mounting method
DIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs)
12.5kA
Construction size
4 modular spacing
Max. continuous voltage AC
335V
Remote signalling
Voltage protection level
1.2kV
Nominal voltage AC
415V
Degree of protection (IP)
IP20
Signalling at the device
Optic
Integrated backup fuse
Energy-coordinated protection effect with regard to the terminal equipment
System configuration TT
Voltage protection level N-PE
1.7kV
System configuration IT
System configuration DC
Max. conductor cross section flexible (fine-strand)
25mm²
Max. conductor cross section solid (solid, stranded)
35mm²
System configuration TN-C
System configuration TN-S
Voltage protection level L-N
1.2kV
System configuration TN
Test class
Type 1 + 2
System configuration TN-C-S
System configuration other
Specific energy (W/R)
15kJ/Ohm
Max. overcurrent protection device, parallel connection (fuse)
160A
Voltage switching spark gap technology
Voltage protection level L-PE
1.7kV
Max. overcurrent protection device, series connection (fuse)
80A