Technical specifications

Number of auxiliary contacts as normally open contact-
Number of auxiliary contacts as normally closed contact1
Overload release current setting60 - 130A
Position of connection for main current circuitFront side
Suitable for DIN rail (top hat rail) mountingYes
DIN rail (top hat rail) mounting optionalYes
Motor drive optionalYes
Number of auxiliary contacts as change-over contact1
Type of control elementToggle
Motor drive integratedNo
Adjustment range undelayed short-circuit release600 - 600A
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseYes
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release600 - 600A
Integrated earth fault protectionYes
Type of electrical connection of main circuitScrew connection
With switched-off indicatorYes
Rated permanent current Iu130A
Number of poles4
Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz36kA