Technical specifications

Release characteristicB
Number of protected poles4
Frequency50 - 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10kA
Built-in depth69mm
Rated voltage440V
Rated current25A
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Voltage typeOther
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Power loss11.52W
Number of poles (total)4
Rated impulse withstand voltage Uimp4kV
Current limiting class3
Rated insulation voltage Ui440V
Pollution degree3
Over voltage category3
Width in number of modular spacings4.0
Concurrently switching neutral conductorNo
Connectable conductor cross section solid-core0.75 - 35mm²
Connectable conductor cross section multi-wired0.75 - 25mm²
Additional equipment possibleYes
Flush-mounted installationNo
Explosion-proofNo
Degree of protection (IP)IP20
Ambient temperature during operating-25 - 55°C
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS274065R0255 | S204MT-B25UC

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Release characteristic

B

Number of protected poles

4

Frequency

50 .. 60Hz

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10kA

Built-in depth

69mm

Rated voltage

440V

Rated current

25A

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Voltage type

Other

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Power loss

11.52W

Number of poles (total)

4

Rated impulse withstand voltage Uimp

4kV

Current limiting class

3

Rated insulation voltage Ui

440V

Pollution degree

3

Over voltage category

3

Width in number of modular spacings

4.0

Concurrently switching neutral conductor

Connectable conductor cross section solid-core

0.75 .. 35mm²

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Additional equipment possible

Flush-mounted installation

Explosion-proof

Degree of protection (IP)

IP20

Ambient temperature during operating

-25 .. 55°C

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.