Technical specifications

Voltage typeOther
Rated current15A
Power loss3.76W
Rated voltage440V
Release characteristicK
Degree of protection (IP)IP20
Current limiting class3
Number of protected poles2
Concurrently switching neutral conductorNo
Width in number of modular spacings2.0
Frequency50 - 60Hz
Over voltage category3
Rated insulation voltage Ui440V
Explosion-proofNo
Pollution degree3
Built-in depth69mm
Connectable conductor cross section solid-core0.75 - 35mm²
Number of poles (total)2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Flush-mounted installationNo
Ambient temperature during operating-25 - 55°C
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Connectable conductor cross section multi-wired0.75 - 25mm²
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10kA
Additional equipment possibleYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS272065R0457 | S202MT-K15UC

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Voltage type

Other

Rated current

15A

Power loss

3.76W

Rated voltage

440V

Release characteristic

K

Degree of protection (IP)

IP20

Current limiting class

3

Number of protected poles

2

Concurrently switching neutral conductor

Width in number of modular spacings

2.0

Frequency

50 .. 60Hz

Over voltage category

3

Rated insulation voltage Ui

440V

Explosion-proof

Pollution degree

3

Built-in depth

69mm

Connectable conductor cross section solid-core

0.75 .. 35mm²

Number of poles (total)

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Flush-mounted installation

Ambient temperature during operating

-25 .. 55°C

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10kA

Additional equipment possible