Aleta.hr

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Rated voltage415V
Number of poles (total)2
Current limiting class3
Power loss2.3W
Rated fault current0.03A
Surge current capacity3kA
Rated short-circuit breaking capacity Icn according to EN 61009-110kA
Number of protected poles1
Frequency50/60 Hz
Rated short-circuit breaking capacity according to EN 6100910kA
Rated insulation voltage Ui500V
Disconnection characteristicUndelayed
Voltage typeAC
Leakage current typeA
Rated current13A
Rated short-circuit breaking capacity according to IEC 60947-225kA
Rated impulse withstand voltage Uimp4kV
Release characteristicC
Over voltage category3
With interlocking deviceNo
Built-in depth91mm
Pollution degree2
Concurrently switching neutral conductorNo
Ambient temperature during operating-25 - 60°C
Connectable conductor cross section multi-wired0.75 - 25mm²
Connectable conductor cross section solid-core- - -mm²
Degree of protection (IP)IP20
Flush-mounted installationNo
Width in number of modular spacings2
Anti-nuisance tripping versionNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CCG001678R0001 | FS401M-C13/0.03

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

415V

Number of poles (total)

2

Current limiting class

3

Power loss

2.3W

Rated fault current

0.03A

Surge current capacity

3kA

Rated short-circuit breaking capacity Icn according to EN 61009-1

10kA

Number of protected poles

1

Frequency

50/60 Hz

Rated short-circuit breaking capacity according to EN 61009

10kA

Rated insulation voltage Ui

500V

Disconnection characteristic

Undelayed

Voltage type

AC

Leakage current type

A

Rated current

13A

Rated short-circuit breaking capacity according to IEC 60947-2

25kA

Rated impulse withstand voltage Uimp

4kV

Release characteristic

C

Over voltage category

3

With interlocking device

Built-in depth

91mm

Pollution degree

2

Concurrently switching neutral conductor

Ambient temperature during operating

-25 .. 60°C

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Connectable conductor cross section solid-core

- .. -mm²

Degree of protection (IP)

IP20

Flush-mounted installation

Width in number of modular spacings

2

Anti-nuisance tripping version