Aleta.hr

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Number of protected poles3
Number of poles (total)4
Rated voltage400V
Rated insulation voltage Ui500V
Rated current16A
Rated fault current0.03A
Rated impulse withstand voltage Uimp4kV
Leakage current typeF
Power loss6.6W
Rated short-circuit breaking capacity according to EN 6100910kA
Current limiting class3
Rated short-circuit breaking capacity Icn according to EN 61009-110kA
Disconnection characteristicUndelayed
Surge current capacity3kA
Rated short-circuit breaking capacity according to IEC 60947-2-kA
Voltage typeAC
Frequency50/60 Hz
Release characteristicB
Over voltage category3
Concurrently switching neutral conductorNo
With interlocking deviceNo
Pollution degree2
Ambient temperature during operating-25 - 60°C
Anti-nuisance tripping versionNo
Width in number of modular spacings4
Degree of protection (IP)IP20
Connectable conductor cross section multi-wired0.75 - 25mm²
Connectable conductor cross section solid-core- - -mm²
Flush-mounted installationNo
Built-in depth91mm
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CCG001742R0001 | FS403MK-B16/0.03

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Number of protected poles

3

Number of poles (total)

4

Rated voltage

400V

Rated insulation voltage Ui

500V

Rated current

16A

Rated fault current

0.03A

Rated impulse withstand voltage Uimp

4kV

Leakage current type

F

Power loss

6.6W

Rated short-circuit breaking capacity according to EN 61009

10kA

Current limiting class

3

Rated short-circuit breaking capacity Icn according to EN 61009-1

10kA

Disconnection characteristic

Undelayed

Surge current capacity

3kA

Rated short-circuit breaking capacity according to IEC 60947-2

-kA

Voltage type

AC

Frequency

50/60 Hz

Release characteristic

B

Over voltage category

3

Concurrently switching neutral conductor

With interlocking device

Pollution degree

2

Ambient temperature during operating

-25 .. 60°C

Anti-nuisance tripping version

Width in number of modular spacings

4

Degree of protection (IP)

IP20

Connectable conductor cross section multi-wired

0.75 .. 25mm²

Connectable conductor cross section solid-core

- .. -mm²

Flush-mounted installation

Built-in depth

91mm