Aleta.hr
Announcement

Registration is currently available to business customers only (B2B).

Details

  • •Earthing, lightning and surge protection
  • •Surge protection device for power supply systems
  • •Minimum order quantity: 1 pcs
  • •ABB

Technical specifications

System configuration DCNo
System configuration TN-CNo
System configuration ITNo
System configuration TN-C-SYes
System configuration TNYes
System configuration TTYes
System configuration otherNo
System configuration TN-SYes
Max. continuous voltage DC-V
Voltage protection level1.5kV
Max. PV-voltage-V
Max. discharge surge current (8/20)20kA
Number of conductors (without earthing)1
Nominal voltage DC-V
Max. continuous voltage AC350V
Short-circuit breaking capacity (Isccr)100kA
Integrated short-circuit protectionNo
Leakage-current freeNo
Voltage protection level L-N-kV
Mounting methodOther
Voltage protection level N-PE-kV
Integrated backup fuseNo
Max. conductor cross section solid (solid, stranded)25mm²
Construction size1 modular spacing
Max. conductor cross section flexible (fine-strand)16mm²
Category type 2Yes
Max. overcurrent protection device, parallel connection (fuse)-A
With remote signalling contactNo
Integrated short-circuit protection selective to fuse gG-A
Signalling at the deviceOptic
Max. overcurrent protection device, series connection (fuse)125A
Nominal discharge surge current (8/20)20kA
Nominal voltage AC230V
Degree of protection (IP)IP20