Technical specifications
MSC-D-32-M32(24VDC)/BBA | Motor-starter combination direct, 24V DC control, Ie=29.3A, Pmax=15kW,

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Motor starter/motor starter combination
- 1 KOM
- EATON
Technical specifications
Type of motor starter
Direct online starter (DOL)
Rated control supply voltage Us at AC 50HZ
0 .. 0V
Voltage type for actuating
DC
Rated operation power at AC-3, 230 V, 3-phase
7.5kW
Rated operation power at AC-3, 400 V
15kW
Rated control supply voltage Us at DC
24 .. 24V
Rated power, 460 V, 60 Hz, 3-phase
0kW
Rated operation current Ie
29.3A
Overload release current setting
25 .. 32A
Rated control supply voltage Us at AC 60HZ
0 .. 0V
Rated operation current at AC-3, 400 V
32A
Rated conditional short-circuit current, type 1, 600 Y/347 V
0A
Rated conditional short-circuit current, type 1, 480 Y/277 V
0A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
1
Power consumption
0.9W
Rated power, 575 V, 60 Hz, 3-phase
0kW
Supporting protocol for AS-Interface Safety at Work
Rated conditional short-circuit current, type 2, 230 V
50000A
With short-circuit release
Rated conditional short-circuit current, type 2, 400 V
50000A
Supporting protocol for DeviceNet Safety
Supporting protocol for INTERBUS-Safety
Supporting protocol for PROFIsafe
Supporting protocol for SafetyBUS p
Supporting protocol for other bus systems
Width
45mm
Height
200mm
Depth
156mm
Ambient temperature, upper operating limit
55°C
Temperature compensated overload protection
Release class
CLASS 10 A
Type of electrical connection of main circuit
Screw connection
Type of electrical connection for auxiliary- and control current circuit
Screw connection
Rail mounting possible
With transformer
Coordination class according to IEC 60947-4-3
Class 2
Number of command positions
0
Suitable for emergency stop
Number of indicator lights
0
Degree of protection (IP)
IP00
Degree of protection (NEMA)
Other
External reset possible
With fuse
Supporting protocol for PROFIBUS
Supporting protocol for INTERBUS
Supporting protocol for CAN
Supporting protocol for ASI
Supporting protocol for Modbus
Supporting protocol for Data-Highway
Supporting protocol for DeviceNet
Supporting protocol for PROFINET IO
Supporting protocol for SUCONET
Supporting protocol for LON
Supporting protocol for TCP/IP
Supporting protocol for PROFINET CBA
Supporting protocol for SERCOS
Supporting protocol for EtherNet/IP